浅谈变压器中性点不接地的问题及解决方法

2015-07-06 10:33来源:能源与节能作者:赵道文关键词:变压器三相不平衡接地系统收藏点赞

投稿

我要投稿

摘要:针对麻家梁选煤厂产品仓配电室高压配电柜连续烧毁情况进行探讨,针对变压器中性点不接地造成中性点移位,提出解决方案,阐述三相负载不平衡产生的原因及危害,并对类似情况的应对方法进行探讨。

关键词:选煤厂;三相不平衡;变压器;中性点移位

On Ungrounded Transformer Problems and Solutions of Ungrounded Neutrals in Transformer

ZHAO Daowen

(Dadi Coal Preparation Engineering Co., Ltd. of Datong Coal Mine Group, Datong 037001, Shanxi, China)

Abstract: According to the burning situation of high-voltage distribution cabinet in product warehouse distribution room in Majiaiang Coal Preparation Plant, and neutral point shift due to ungrounded neutrals in transformer, this paper proposed solutions, explained the reasons and hazards for the three-phase load imbalance, and the ways to deal with similar situation were discussed.

Keywords: coal preparation plant; unbalance three phase circuit; transformer; neutral point shift

中图分类号:TM411+.2 文献标识码:A 文章编号:

0 引言

麻家梁选煤厂属于同煤集团浙能麻家梁煤业公司配套选煤厂,年产1 200×104 t,有亚洲最大立井之称。位于山西省朔州市朔南红旗牧场,属于特大动力型选煤厂,选煤厂配电和控制水平达到国内一流水平,满足国家最新选煤设计规范所规定的一级装备水平。矿井建设110 kV变电站,架设两回路供电专线,一路从朔州市安荣220 kV变电站引入,另一路从宁武110 kV变电站引入。选煤厂电源由麻家梁矿井主井井口房配电室提供两回不同母线出线,经电缆引至选煤厂10 kV高压配电室,两回电源线路分列运行。同时向原煤变配电室、产品仓变配电所各提供一回10 kV电源。选煤厂10 kV高压系统设计为中性点不接地系统,主变压器(10 A/0.69 kV)采用中性点经高阻接地系统,并在660 V供配电回路中设置漏电保护。380 V/220 V低压配电采用中性点直接接地系统。产品仓配电室和主厂房配电室各有一台10 A/0.4 kV变压器,分别为主厂房和产品系统提供控制、照明等设备供电。高压配电柜使用无锡中科KYN44A-12系列配电柜,高压接触器采用进口ABB VSC 12,均属于国内外先进产品。